Micro Switch Knowledge Center › Micro switch wiring

A micro switch has three standard terminals: COM (common), NO (normally open) and NC (normally closed). Power enters COM; at rest COM is connected to NC, and when the actuator is pressed COM transfers to NO. Most wiring problems come from confusing the NO and NC terminals, from switching the neutral instead of the live conductor, or from relying on an NC circuit without checking that the released state is the safe state.

Terminal identification

ターミナル Symbol State at rest State when actuated
Common COM / C Connected to NC Connected to NO
Normally open NO Open circuit Closed circuit
Normally closed NC Closed circuit Open circuit

Terminals are marked on the body, in the datasheet drawing and in the ordering code. On quick-connect versions the terminals are typically 2.8 mm or 4.8 mm spade tabs; on PCB versions the pin layout is shown in the drawing.

SPDT wiring: the standard control circuit

In an SPDT micro switch, COM is the moving contact and NO/NC are the two fixed contacts. A typical wiring is:

  1. Connect the supply (after the fuse or breaker) to COM.
  2. Connect the NC terminal to the circuit that must be live when the actuator is not pressed — for example, a door interlock that cuts power when the door opens.
  3. Connect the NO terminal to the circuit that must only run when the actuator is pressed — for example, a start or presence signal.

Only one of NO and NC is energised at a time. The unused terminal may be left unconnected, but if it is left floating inside a metal enclosure it should be insulated.

NC wiring for fail-safe circuits

Safety interlocks normally use the NC contact. If the actuator is released, the wire breaks or the switch fails mechanically, the circuit opens and the machine stops. Wiring the interlock through NO would fail dangerous: a broken wire would look identical to “not pressed”.

For higher-risk machinery, use two NC switches in series (or a dual-channel safety relay) so a single fault cannot defeat the interlock.

Wiring an SPST micro switch

An SPST micro switch has only two terminals:

  • SPST-NO: the circuit closes when actuated. Used for start buttons, presence detection and “door closed” signals.
  • SPST-NC: the circuit opens when actuated. Used for simple stop and interlock functions.

SPST versions are cheaper and smaller, but they cannot provide both states and have no fail-safe behaviour unless the NC type is used.

AC and DC considerations

Aspect AC circuits DC circuits
Arcing Self-extinguishing at zero crossing Arcs persist; DC rating is usually lower than AC
Rating to use AC rating at the actual voltage DC rating at the actual voltage — never assume the AC value applies
Inductive loads Add RC snubber or varistor Add flyback diode across the coil
Low-level signals Not typical Use a low-level rated switch (e.g. 100 mA 30 VDC)

Step-by-step wiring procedure

  1. Isolate and lock out the supply; verify dead with a tester.
  2. Identify COM, NO and NC from the switch marking and datasheet.
  3. Decide the safe state: which circuit must be live when the actuator is released?
  4. Crimp the correct terminals (match tab width) and pull-test each connection.
  5. Route conductors away from moving parts and sharp edges; leave a service loop.
  6. Restore power and test both states with a meter before connecting the load.
  7. Record the wiring in the machine documentation, including the terminal used for the interlock.

Common wiring mistakes

  • Swapping NO and NC, which inverts the logic and can make an interlock fail dangerous.
  • Switching the neutral instead of the live conductor, leaving the load live when “off”.
  • Using a 125 VAC-rated switch on a 250 VAC circuit or on DC at the same voltage.
  • Over-tightening spade terminals and cracking the switch housing.
  • Assuming a sealed switch can be immersed: IP67 protects against dust and temporary immersion, not continuous submersion.

Frequently asked questions

Which terminal is COM on a micro switch?

COM is normally the centre terminal, with NO and NC on either side, and is marked on the body or shown in the datasheet drawing. Always confirm against the drawing rather than by position alone.

Does it matter which way round NO and NC are wired?

Yes. Wiring determines the logic and the safe state. An interlock must use NC so that a broken wire or released actuator stops the machine.

Can I use a micro switch as a door interlock?

Yes, and it is one of the most common uses. Wire the NC contact in series with the load so that opening the door removes power.

What is the difference between SPDT and DPDT?

SPDT switches one circuit between two states. DPDT contains two independent SPDT circuits operated by the same actuator, used for reversing motors or switching two circuits at once.